Produal Differential Pressure Transmitter PEL Series

Click to enlarge image

 Origin

Finland

 Model Number

PEL series

 Brand Name

Produal


PEL Series

  

PEL

PEL is a pressure transmitter detecting pressures and pressure differences of the air-handling system. 
The proper range of measuring can be chosen at commissioning. The outputs are directly proportional to the pressure difference between inlets + and -. 
The drift of the 0-point is compensated by software making regularly and automaticly 0-point calibration. 
No re-calibration is normally needed. 
The influence of process disturbances can be damped by selecting suitable time constant (Output delay = 8s). 
Displays can be incorporated also after commissioning by replacing the cover with a display cover and by connecting the displays to the connector on the printed board card. The resolution of digital display is 0,1 Pa for measured values below 200Pa. 
Due to the IP 54 enclosure PEL can also be used in dusty and wet surroundings. 

Measuring ranges 0...100Pa ± 50Pa
  0...200Pa ± 100Pa
  0...500Pa ± 250Pa
  0...1000Pa ± 500Pa

 

 PEL-2500

 

PEL 2500 is a pressure transmitter detecting pressures and pressure differences of the air-handling system. Pressure- or flow linear output can be selected at the commissioning. Display is always in Pascals.

The drift of the 0-point is automatically calibrated and compensated every ~5 minutes. No re-calibration is normally needed.
The influence of process disturbances (e.g. turbulence) can be damped by selecting suitable time constant (2s or 8s).
Connections to the detected process are made by using Ø 6/4 mm plastic tubes. The proper range of measuring can be chosen at commissioning.
Displays can be incorporated also after commissioning by replacing the cover with a display cover and by connecting the displays to the connector on the printed board card. The resolution of digital display is 0,1 Pa for measured values below 200Pa.
Due to the IP 54 enclosure PEL 2500 can also be used in dusty and wet surroundings.

Measuring ranges ± 100Pa 0...1000Pa
  0...100Pa 0...1500Pa
  0...200Pa 0…2000Pa
  0...500Pa 0…2500Pa

  

PEL-25K

 

PEL 25K is a pressure transmitter detecting pressures and pressure differences of the air-handling system.
The drift of the 0-point is automatically calibrated and compensated every ~5 minutes. No re-calibration is normally needed.
The influence of process disturbances (e.g. turbulence) can be damped by selecting suitable time constant (2s or 8s).
Connections to the detected process are made by using Ø 6/4 mm plastic tubes. The proper range of measuring can be chosen at commissioning. The outputs are directly proportional to the pressure difference between inlets + and -.
The resolution of digital displays is 10 Pa. Displays can be incorporated also after commissioning by replacing a normal cover with a display cover and by connecting the displays to the connector on the printed board card.
Due to the IP 54 enclosure PEL 25K can also be used in dusty and wet surroundings.

Measuring ranges 0...2kPa 0...4kPa
  0...5kPa 0...7kPa
  0...10kPa 0...15kPa
  0...20kPa 0...25kPa

 

 

 